Chapter 4. Rack Information

This chapter describes the physical characteristics of the tall (42U) ICE 8200 racks in the following sections:

Overview

At the time this document was published only the tall (42U) Altix ICE rack (shown in Figure 4-2) was approved for use with the ICE systems.

Altix ICE 8200 Series Rack (42U)

The tall rack (shown in Figure 4-1) has the following features and components:

  • Front and rear door. The front door is opened by grasping the wide end of the triangle-shaped door piece and pulling outward. It uses a key lock for security purposes that should open all the front doors in a multi-rack system (see Figure 4-2). Note that the front door and rear door locks are keyed differently. The optional water-chilled rear door does not use a lock.

    The rear door has a push-button key lock to prevent unauthorized access to the system. The rear doors have a master key that locks and unlocks all rear doors in a system made up of multiple racks. You cannot use the rear door key to secure the front door lock.

  • Cable entry/exit area. Cable access openings are located in the front floor and top of the rack. Cables are only attached to the front of the IRUs; therefore, most cable management occurs in the front and top of the rack. Stand-alone administrative, leader and login server modules are the exception to this rule and have cables that attach at the rear of the rack. Rear cable connections will also be required for optional storage modules installed in the same rack with the IRU(s). Optional inter-rack communication cables pass through the top of the rack. I/O and power cables normally pass through the bottom of the rack.

  • Rack structural features. The rack is mounted on four casters; the two rear casters swivel. There are four leveling pads available at the base of the rack. The base of the rack also has attachment points to support an optional ground strap, and/or seismic tie-downs.

  • Power distribution units in the rack. Fifteen outlets are required for a single IRU system:

    • 8 outlets for an IRU

    • 4 outlets for administration and RLC servers

    • 2 outlets for a service node (server)

    • 1 outlet for the rack lighting feature

    • Allow 8 more outlets for each additional IRU in the system


      Note: Single phase PDUs for the rack come in 8 and 5-outlet versions. At time of publication, the 5-outlet version was being discontinued as a standard item for new systems.


    Two single-phase power distribution units (PDUs) are needed for a base rack system,
    (8 outlets per PDU). Three of the 5-outlet single-phase PDUs are required for a base system. A three-phase power distribution unit has 18 outlet connections, 16 of them are needed to power two IRUs.

    Figure 4-1. Altix ICE 8200 Series Rack Example

    Altix ICE 8200 Series Rack Example

    Figure 4-2. Front Lock on Tall (42U) Altix Rack

    Front Lock on Tall (42U) Altix Rack

Technical Specifications

Table 4-1 lists the technical specifications of the Altix ICE 8200 series tall rack.

Table 4-1. Tall Altix Rack Technical Specifications

Characteristic

Specification

Height

79.5 in. (201.9 cm)

Width

31.3 in. (79.5 cm)

Depth

45.8 in. (116.3 cm)

Weight (full)

2,200 lbs. (1,000 kg) approximate

Shipping weight (max)

2,450 lbs. (1,113.6 kg) approximate

Voltage range

Nominal

Tolerance range

North America/International

200-240 VAC /230 VAC

180-264 VAC /180-254 VAC

Frequency

Nominal

Tolerance range

North America/International

50/60 Hz /50 Hz

47-63 Hz /47-63 Hz

Phase required

Single-phase or 3-phase

Power requirements (max)

31.63 kVA (31 kW)

Hold time

20 ms

Power cable

12 ft. (3.66 m) pluggable cords